MAN0575-04-EN
PAGE 80 of 97
© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.
Profibus Modules User Manual
EO 09-0009
Example of a CSV file, which was exported to Excel:
Cell Parameter Value Meaning
A1 Station Address 1 Station address of the PROFIBUS Slave device.
B1 Record Type 2 The Record Type is always 2.
C1 IdentNumber 7501 (0x049F) IdentNumber of the Slaves.
D1 VendorNumber 0 No Vendor number is available.
E1 VendorName Horner APG Vendor name of the device.
F1 Device HE800PBS600-001 Description of the device.
G1 Description PC_Slave
Description of the device, which is also shown in SyCon as the
name of the device.
H1 MasterAddress 1 Address of the related Master.
I1 Settings 0
The addressing mode (byte- or word addressing) and the data
format of the process data are shown. The descriptions you see in
section
Description of the Parameter Settings.
J1 Reserved Reserved Reserved
K1 ModulCount 2
Number of the modules of the device. For each modul the
information with data type, data size, data position and the offset
address follow. The information for
modul 1 you find in the cells L1, M1, N1, O1 and for
modul 2 in the cells P1, Q1, R1, S1.
L1 Data Size 4 The size of the modul is 4 bytes.
M1 Data Type 21 Input; Data type unsigned Integer 8
N1 Data Position 0 Output; Data type unsigned Integer 8
O1 Offset address 10 4 Byte-Modul starting with the offset address 10.
P1 Data Size 4 The size of the modul is 4 bytes.
Q1 Data Type 37 Output; Data type unsigned Integer 8
R1 Data Position 0 Data position of the second modul.
S1 Offset address 20 4 Byte-Modul starting with the offset address 10.
T1...IQ1 ... 0
The modules 3 till 59 are not used for this device and so a 0 is
shown.
Figure 58: Example of a CSV File in Excel
If two or more Slave devices are connected to the Master, these are displayed in the next lines of the