Horner-apg QX351 OCS HEQX351C103 Manual do Utilizador Página 49

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 109
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 48
MAN0892-03-EN CH.10
February 25, 2010 Page 49 of 109 #1039
The View Protocols Sub-Menu displays two System Settings, none of which are editable.
As mentioned earlier, MJ1 (Port 1) and MJ2 (Port 2) serial ports support downloadable protocols. To
assign a downloadable protocol to a QX351 serial port, select the Protocol Config item in Cscape’s
Program menu and then setup a protocol for Port 1 or Port 2 (or both of them).
In the View Protocols Sub-Menu, the currently downloaded protocol, if any, and its version number are
displayed for the respective port.
Port 1:
Protocol name = (None Loaded) or name of the protocol assigned to MJ1
Protocol version = Blank or version of the protocol assigned to MJ1
Port 2:
Protocol name = (None Loaded) or name of the protocol assigned to MJ2
Protocol version = Blank or version of the protocol assigned to MJ2
Set Fkeys
The Set Fkeys Sub-Menu displays two System Settings, both of which are editable.
Fkeys: Momentary (default) = %K1-5 bits go On/Off as F1-F5 are pressed / released
Toggle = %K1-5 bits toggle each time F1-F5 are pressed
SYS_Fn enable: Yes (default) = Reset and all clear, system functions enabled
No = Reset and all clear, system functions disabled
Vista de página 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 108 109

Comentários a estes Manuais

Sem comentários