MAN0964-01-EN CH.16
June 29, 2012 Page 103 of 122
Figure 16.3 Backup Registers
Restore OCS Data:
When initiated, this will allow the user to manually copy the backed up data from the onboard FLASH to
the Battery-Backed RAM.
A restore operation will be automatically initiated if a backup has been previously created and on power-
up the Battery-Backed RAM registers fail their check.
The following process will be followed for restoring data:
The controller will be placed in IDLE mode.
Data will be copied from onboard FLASH to OCS Battery-Backed RAM
The controller will reset.
The controller will be put in RUN mode if the AutoRun setting is ‘Yes’ else it will remain in IDLE
mode.
Figure 16.4 Restore OCS Data
%SR164.3 is set to 1 only when an automatic restore operation is performed - not on a manual one. This
bit is reset to 0 when a new backup is created.