MAN0872-06-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
12/18/2008 Page 3 of 4 ECN # 947
5 Filter
Filter Constant sets the level of digital filtering according to the
following chart.
60
20
10040 8020
0
10
100
90
80
70
60
50
40
30
Scans0
1
2 3 4 5 60 7
%Complete [ ]
Filter
Constant
Digital Filtering. The illustration above demonstrates the
effect of digital filtering (set with Filter
Constant) on module response to a
temperature change.
6 I/O Register Map
7 MJ2 Pinouts in Full and Half Duplex Modes
Registers
Description
%I1 to %I24 Digital Inputs
%I32 Output Fault
%I25 to %I31 Reserved
%Q1 to %Q16 Digital outputs
%Q17 Clear HSC1 accumulator to 0
%Q18
Totalizer: Clear HSC2
Quadrature 1-2: Accumulator 1
Reset to max – 1
%Q19 Clear HSC3 Accumulator to 0
%Q20
Totalizer: Clear HSC4
Quadrature 3-4: Accumulator 3
Reset to max – 1
%Q21 to %Q32 Reserved
%AI1 to %AI4 Analog inputs
%AI5, %AI6 HSC1 Accumulator
%AI7, %AI8 HSC2 Accumulator
%AI9, %AI10 HSC3 Accumulator
%AI11, %AI12 HSC4 Accumulator
Full Duplex Mode
Half Duplex Mode
Pin MJ2 Pins
Signal Direction
8
TXD OUT
7
RXD IN
6
0 V Ground
5*
+5 60mA OUT
4
TX- OUT
3
TX+ OUT
2
RX- IN
1
RX+ IN
1
8
* +5Vdc 60mA max
Pin MJ2 Pins
Signal Direction
8
TXD OUT
7
RXD IN
6
0 V Ground
5*
+5 60mA OUT
4
TX- OUT
3
TX+ OUT
2
TX-/RX- IN/OUT
1
TX+/RX+ IN/OUT
1
8
* +5Vdc 60mA Max
%AQ1, %AQ2 PWM1 Duty Cycle
%AQ3, %AQ4 PWM2 Duty Cycle
%AQ5, %AQ6 PWM Prescale
%AQ7, %AQ8 PWM Period
%AQ9 to %AQ14 Analog outputs
Note: Not all XLt units contain the I/O listed in this table.
Registers PWM HSC Stepper
%AQ1
Start
Frequency
%AQ2
PWM1 Duty
Cycle
(32 bit)
HSC1
Preset
Value
Run
Frequency
%AQ3
%AQ4
PWM2 Duty
Cycle
(32 bit)
HSC2
Preset
Value
Accel Count
(32 bit)
%AQ5
%AQ6
PWM Prescale
(32 bit)
Run Count
(32 bit)
%AQ7
%AQ8
PWM Period
(32 bit)
Decel Count
(32 bit)
%Q1 Run
%I30 Ready/Done
%I31
Error